Configure Discrete Output Fault Action - Emerson Micro Motion 2500 Configuration And Use Manual

Transmitters with configurable input/outputs
Hide thumbs Also See for Micro Motion 2500:
Table of Contents

Advertisement

Integrate the meter with the control system
6.4.3

Configure Discrete Output Fault Action

ProLink III
Field Communicator
Overview
Discrete Output Fault Action controls the behavior of the Discrete Output if the
transmitter encounters an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement
the fault action until the timeout has elapsed.
CAUTION!
Do not use Discrete Output Fault Action as a fault indicator. If you do, you may not be able to
distinguish a fault condition from a normal operating condition. If you want to use the Discrete
Output as a fault indicator, set Discrete Output Source to Fault and set Discrete Output Fault
Action to None.
Procedure
Set Discrete Output Fault Action as desired.
The default setting is None.
Related information
Options for Discrete Output Fault Action
Label
Upscale
Downscale
None (default)
96
Device Tools > Configuration > Fault Processing
Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO 1 Fault Action
Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO 2 Fault Action
Fault indication with the Discrete Output
Micro Motion Model 2500 Transmitters with Configurable Input/Outputs
Discrete Output behavior
Fault: Discrete Output is ON (site-specific voltage)
No fault: Discrete Output is controlled by its assign-
ment
Fault: Discrete Output is OFF (0 V)
No fault: Discrete Output is controlled by its assign-
ment
Discrete Output is controlled by its assignment

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents