Emerson Micro Motion 2500 Configuration And Use Manual page 223

Transmitters with configurable input/outputs
Hide thumbs Also See for Micro Motion 2500:
Table of Contents

Advertisement

Table C-1:
Transmitter default values and ranges
Type
Parameter
Special units
Base mass unit
Base mass time
Mass flow conversion factor
Base volume unit
Base volume time
Volume flow conversion factor
Variable map-
Primary variable
ping
Secondary variable
Tertiary variable
Quaternary variable
mA Output 1
Primary variable
LRV
URV
AO cutoff
AO added damping
LSL
USL
MinSpan
Fault action
AO fault level – downscale
AO fault level – upscale
Last measured value timeout
mA Output 2
Secondary variable
LRV
URV
AO cutoff
AO added damping
Configuration and Use Manual
(continued)
Default
Range
g
sec
1
L
sec
1
Mass flow
Density
Mass flow
Volume flow
Mass flow
–200.00000
g/s
200.00000 g/s
0.00000 g/s
0.00000 sec
–200 g/s
200 g/s
0.3 g/s
Downscale
2.0 mA
1.0 – 3.6 mA
22 mA
21.0 – 24.0 mA
0.00 sec
Density
0.00 g/cm3
10.00 g/cm3
Not-A-Number
0.00000 sec
Default values and ranges
Comments
The user-entered value is correc-
ted down to the nearest lower
value in a list of preset values.
Read-only.
LSL is calculated based on the
sensor size and characterization
parameters.
Read only.
USL is calculated based on the
sensor size and characterization
parameters.
Read-only.
215