WEG CFW100 Programming Manual page 117

Micro mini drives
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

READ
P009 - Motor Torque
Range:
Properties:
Description:
It indicates the torque developed by the motor in relation to the rated torque.
P030 - Module Temperature
Range:
Properties:
Description:
The temperature of the power module is monitored and indicated in parameter P030 in degrees Celsius. This value
is constantly compared to the overtemperature fault and alarm tripping value of the power module F051 and A050,
according to
Table 11.1 on page
In addition to the indication of alarm A050, the overtemperature protection gradually reduces the switching
frequency to 2.5 kHz. This overtemperature protection characteristic can be disabled in the control configuration
parameter P397.
NOTE!
The default setting of P397 meets most application needs of the inverter. Therefore, avoid modifying
its content without knowing the related consequences. If you are not sure, contact WEG Technical
Assistance before changing P397.
P038 - Encoder Speed
Range:
Properties:
11
Description:
This parameter presents the instant speed of the encoder in revolutions per minute (RPM); the measurement is not
filtered and it is updated every 6 ms.
P039 - Encoder Pulses Count
Range:
Properties:
Description:
Using this parameter it is possible to check the number of pulses counted from the encoder in quadrature. The
count can be incremented from 0 to 9999 (clockwise) or decremented from 9999 to 0 (counterclockwise).
11-4 | Micro Mini Drives
-200.0 to 200.0 %
ro, VVW
-200.0 to 200.0 ºC
ro
11-4.
Table 11.1: Overtemperature actuation levels of the power module
Line
Frame Size
200 V
A
200 V
B
400 V
A, B e C
-9999 to 9999 rpm
ro
0 to 9999
ro
Level A050
Level F051
90 °C (194 °F)
100 °C (212 °F)
116 °C (248 °F)
126 °C (258 °F)
100 °C (212 °F)
110 °C (222 °F)