P045 - Fan Enabled Time
Range:
0 to FFFF (hexa)
Properties:
ro
Description:
It indicates the total number of hours that the heatsink fan remained connected. This value is kept even when the
inverter is disconnected.
P047 - CONF Status
Range:
0 to 33
Properties:
ro
Description:
This parameter shows the source situation of the CONFIG mode. The
CONFIG status.
P047
0
Out of CONFIG status. The HMI and parameters P006 and P680 must not indicate ConF
1
Two or more DIx (P263...P270) programmed for (4 = Forward Run)
2
Two or more DIx (P263...P270) programmed for (5 = Reverse Run)
3
Two or more DIx (P263...P270) programmed for (6 = Start)
4
Two or more DIx (P263...P270) programmed for (7 = Stop)
5
Two or more DIx (P263...P270) programmed for (8 = Direction of Rotation)
6
Two or more DIx (P263...P270) programmed for (9 = LOC/REM)
7
Two or more DIx (P263...P270) programmed for (11 = Accelerate E.P.)
8
Two or more DIx (P263...P270) programmed for (12 = Decelerate E.P.)
9
Two or more DIx (P263...P270) programmed for (14 = 2nd Ramp)
10
Reserved
11
Two or more DIx (P263...P270) programmed for (24 = Disable Flying Start)
12
Two or more DIx (P263...P270) programmed for (26 = Programming Off)
13
Reserved
14
Reserved
15
DIx (P263...P270) programmed for (4 = Forward Run) without DIx (P263...P270) programmed for (5 = Reverse Run) or the
opposite
16
DIx (P263...P270) programmed for (6 = Start) without DIx (P263...P270) programmed for (7 = Stop) or the opposite
17
P221 or P222 programmed for (8 = Multispeed) without DIx (P263...P270) programmed for (13 = Multispeed) or the opposite
18
P221 or P222 programmed for (7 = E.P.) without DIx (P263...P270) programmed for (11 = Accelerate E.P) or the opposite
19
P224 programmed for (1 = DIx) OR P227 programmed for (1 = DIx) without DIx (P263...P270) programmed for (1 = Run/Stop)
AND without DIx (P263...P270) programmed for (2 = General Enable) AND without DIx (P263...P270) programmed for (3 =
Quick Stop) AND without DIx (P263...P270) programmed for (4 = Forward Run) AND without DIx (P263...P270) programmed
for (6 = Start)
20
Reserved
21
P221 or P222 programmed for (8 = Multispeed) with DI1 (P263) AND DI2 (P264) OR DI1 (P263) AND DI5 (P267) OR DI1 (P263)
AND DI6 (P268) OR DI2 (P264) AND DI5 (P267) OR DI2 (P264) AND DI6 (P268) OR DI5 (P267) AND DI6 (P268) programmed
for (13 = Multispeed)
22
Minimum Frequency Reference (P133) greater than Maximum Frequency Reference (P134)
23 to 28
Reserved
29
Two or more DIx (P263...270) programmed for (49 = Enable Fire Mode) OR two or more DOx (P275...P278) Programmed for
(45 = Fire Mode OR P580 programmed for 1, 2 or 4 (Fire Mode Enabled) without DIx programmed for (49 = Enable Fire Mode)
OR DIx programmed for (49 = Enable Fire Mode) OR DOx programmed for (47 = Fire Mode) and P580 programmed for (0 =
Fire Mode Disabled) or (3 = Reserved)
30 to 32
Reserved
33
Parameterization in conflict with DC Bus Compensation. Energy Saver active (P588 value other than zero), Controle VVW ativo
(P202 = 5), Functions Ride-Through or Flying Start are enable (P320 value other than zero)
Table 11.2: Situations for CONFIG status
Condition
Table 11.2 on page 11-5
Micro Mini Drives | 11-5
READ
describes the
11