WEG CFW100 Programming Manual page 142

Micro mini drives
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

APPLICATIONS
P910 - PID Controller Application Version
Range:
Properties:
Description:
Read-only parameter which presents the software version of the PID controller application developed for the
SoftPLC function of frequency inverter.
P911 - Control Setpoint
Range:
Description:
This parameter defines the setpoint value in automatic mode for the PID controller in engineering unit when the
control setpoint source is programmed to be via HMI or communication networks (P920=0). When the control
setpoint source is programmed for some other source (P920≠0), this parameter will show the present setpoint in
automatic mode for the PID controller.
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P912 - Control Setpoint 1
P913 - Control Setpoint 2
P914 - Control Setpoint 3
P915 - Control Setpoint 4
Range:
Description:
These parameters define the setpoint value in automatic mode of the PID controller in engineering unit when the
control setpoint source is programmed to be via logical combination of digital inputs DI3 and DI4 (P950 = 4, 5 or
6) according to
Table 14.6 on page
NOTE!
These parameters will be viewed according to the selection of the parameters for the SoftPLC
engineering unit (P510 and P511).
P916 - Control Process Variable
Range:
Properties:
Description:
14
Read-only parameter which presents the value of the PID controller process variable according to the source defined
in P921 and scale defined in P922 and P923.
14-6 | Micro Mini Drives
0.00 to 90.00
ro
-99.99 to 99.99
-99.99 to 99.99
14-9.
-99.99 to 99.99
ro

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cfw300

Table of Contents