I/O
P282 - Fx Hysteresis
Range:
Description:
This parameter sets the hysteresis on the output frequency signal Fx and on the ramp input F* of the digital relay
output.
In this way, the relay commutation levels are "P281 + P282" and "P281 - P282".
P290 - Ix Current
Range:
Description:
Current level to activate the relay output in the Is > Ix (6) and Is < Ix (7) functions. The actuation occurs on a
hysteresis with upper in P290 and lower level in: P290 - 0.05 x P295, that is, the equivalent value in Amperes for
5 5 % of P295 below P290.
P293 - Tx Torque
Range:
Description:
Torque percentage level to activate the relay output in the Torque > Tx (8) and Torque < Tx (9) functions. The
actuation occurs on a hysteresis with upper level in P293 and lower level in: P293 - 5 %. This percentage value
is related to the motor rated torque matched to the inverter power, and it is expressed in percentage of the motor
rated current (P401 = 100 %).
P695 - DOx Value
9
Range:
Properties:
Description:
Parameters used for monitoring and controlling the inverter by using the communication interfaces. For a detailed
description, refer to the user manual of the communication network, available for download on the website:
www.weg.net.
9-24 | Micro Mini Drives
0.0 to 15.0 Hz
0.0 to 40.0 A
0 to 200 %