NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P925 - Time for Low Level Fault for the Control Process Variable
Range:
0.0 to 999.9 s
Description:
This parameter defines how long the low level alarm condition should remain so that the control process variable
(A760) will generate fault "F761: Low Level Fault of the Control Process Variable".
✓
NOTE!
Setting it to "0.0 s" disables the low level fault for the control process variable.
P926 - Value for High Level Alarm for the Control Process Variable
Range:
-99.99 to 99.99
Description:
This parameter defines the value above which the high level alarm will be generated for the control process variable
(A762).
✓
NOTE!
Setting it to "0" disables the high level alarm and fault for the control process variable.
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P927 - Time for High Level Fault for the Control Process Variable
Range:
0.0 to 999.9 s
Description:
This parameter defines how long the high level alarm condition should remain so that the control process variable
(A762) will generate fault "F763: High Level Fault of the Control Process Variable".
✓
NOTE!
Setting it to "0.0 s" disables the high level fault for the control process variable.
P928 - Selection of the PID Controller Control Action
Range:
0 = Disable PID Controller
1 = Enable PID Controller in Direct Mode
2 = Enable PID Controller in Reverse Mode
Properties:
cfg
Description:
APPLICATIONS
Micro Mini Drives | 14-11