NOTE!
It is not recommended setting the motor rated current greater than inverter rated current (P295).
P402 - Motor Rated Speed
Range:
0 to 24000 rpm
Properties:
cfg, VVW
Description:
It defines the rated motor speed. Parameter P402 must be set according to the information on the motor nameplate.
The setting of parameter P402 via HMI for values above 9999 rpm is performed from 10.00 to 30.00 rpm (x 1000).
P403 - Motor Rated Frequency
Range:
0 to 400 Hz
Properties:
cfg, VVW
Description:
It defines the rated motor frequency. Parameter P403 must be set according to the information on the motor
nameplate.
P404 - Motor Rated Power
Range:
0 = 0.16 HP (0.12 kW)
1 = 0.25 HP (0.18 kW)
2 = 0.33 HP (0.25 kW)
3 = 0.50 HP (0.37 kW)
4 = 0.75 HP (0.55 kW)
5 = 1.00 HP (0.75 kW)
6 = 1.50 HP (1.10 kW)
7 = 2.00 HP (1.50 kW)
8 = 3.00 HP (2.20 kW)
9 = 4.00 HP (3.00 kW)
10 = 5.00 HP (3.70 kW)
11 = 5.50 HP (4.00 kW)
12 = 6.00 HP (4.50 kW)
13 = 7.50 HP (5.50 kW)
14 = 10.00 HP (7.50 kW)
Properties:
cfg, VVW
Description:
It defines the rated motor power. Parameter P404 must be set according to the information on the motor
nameplate.
P405 - Encoder Pulses Number
Range:
32 to 9999
Properties:
cfg, VVW
Description:
MOTOR CONTROL