I/O
reference from the minimum point (0 V / 0 mA / 4 mA or 10 V / 20 mA), and it will be directly related to the minimum
frequency set in P133. Check
If the parameter is set as Active (P230 = 1), the signal in the analog inputs will have a dead zone, where the frequency
reference remains at the Minimum frequency value (P133), even with the variation of the input signal. Check
9.2 on page
9-2.
Reference
P134
P133
0..........................................10 V
0..........................................20 mA
4 mA...................................20 mA
10 V.......................................0
20 mA...................................0
20 mA...................................4 mA
P231 - AI1 Signal Function
P236 - AI2 Signal Function
9
Range:
Properties:
Description:
These parameters define the analog inputs functions.
When the 0 option (Speed Reference) is selected, the analog input can provide the frequency reference for the
motor, subject to the specified limits (P133 and P134) and to the action of the ramps (P100 to P103). However, it
is also necessary to configure parameters P221 and/or P222 by selecting the analog input. For further details, see
9-2 | Micro Mini Drives
Figure 9.2 on page
Signal AIx
(a) Inactive
Figure 9.2: (a) and (b) Actuation of the analog inputs with dead zone
0 = Speed Ref.
1 to 3 = Not Used
4 = PTC
5 to 6 = Not Used
7 = PLC Use
8 = Application Function 1
9 = Application Function 2
10 = Application Function 3
11 = Application Function 4
12 = Application Function 5
13 = Application Function 6
14 = Application Function 7
15 = Application Function 8
16 = Control Setpoint
17 = Process Variable
cfg
9-2.
Reference
P134
P133
0...........................................10 V
0...........................................20 mA
4 mA....................................20 mA
10 V.......................................0
20 mA....................................0
20 mA....................................4 mA
Signal AIx
(a) Active
Figure