P299 - DC Braking Start Time
Range:
0.0 to 15.0 s
Properties:
V/f, VVW
Description:
DC braking duration at the start.
P300 - DC Braking Stop Time
Range:
0.0 to 15.0 s
Properties:
V/f, VVW
Description:
DC Braking duration at the
Output
frequency
Active
DIx - Run/Stop
(a) Run/Stop
During the braking process, if the inverter is enabled, the braking is interrupted and the inverter will start operating
normally.
Output frequency
Direct current
injection at start
P299
DC braking
Run
Stop
Figure 8.8: DC Braking actuation at start
stop.Figure 8.9 on page 8-11
Injection of
DC current
P300
P301
Tempo
Inactive
Figure 8.9: (a) and (b) DC Braking actuation at start with command
Time
P302
Time
shows the braking behavior at the stop.
Output
frequency
Active
DIx - General Enable
(b) General Enable
MOTOR CONTROL
P300
Time
Inactive
Micro Mini Drives | 8-11
8