B. Parameters and data of the CPX terminal
Module parameter: Monitoring of the CPX module
Modules
Depending on the monitoring function for modules with digital and analogue
inputs and outputs (see description on the respective module)
Function no.
4828 + m * 64 + 0
Description
Monitoring of the possible faults can be activated or deactivated (suppressed)
for each module independently. Active monitoring causes the following. The
fault is:
Monitoring
Bit
Description
0
Short circuit/overload in sensor supply (SCS)
1
Short circuit/overload at the outputs (SCO)
2
Undervoltage of outputs/valves (V
3
Short circuit at the valve (SCV)
4
Reserved
5
Reserved
6
Reserved
7
Monitoring parametrisation faults
Values
1 = active (presetting)
0 = inactive
Note
Monitoring can also be set for the complete CPX terminal (see System parame
ter monitoring").
Tab. B/12: Monitoring the CPX module
B−16
Sent to the CPX bus node
Displayed by the module common error LED.
For parametrising the Monitoring CP modules" on the
CPX−CP interface see the manual for the CPX−CP interface
type P. BE−CPX−CP−....
m = module number (0 ... 47)
)
OUT/VAL
Festo P.BE−CPX−SYS−EN en 0902e
[Monitor]
[Monitor SCS]
[Monitor SCO]
[Monitor Vout/val]
[Monitor SCV]
[Monitor parameters]
[Active]
[Inactive]