System Parameter System Idle Mode - Festo CPX System Manual

Installing and commissioning cpx terminals
Table of Contents

Advertisement

C. General information on parametrisation
System parameters
System Idle mode
Tab. C/6: System parameter System Idle mode
Module parameters Settings
Idle mode
Idle state
Digital signal
Analogue signal
Tab. C/7: Module parameters Idle mode" and Idle state"
Festo P.BE−CPX−SYS−EN en 0902e
Settings
Reset outputs
(presetting)
Hold last state
Assume Idle mode
value
If Accept fault mode value" is activated, the signal states
defined by module parameter for the relevant channel will
become effective (see Tab. C/7).
Hold last state
Idle state
(presetting)
Reset output
(presetting)
Set output
Analogue value
Mode of operation
Functionally identical to Fail−safe parametrisation (see also
Fig. C/8 and Fig. C/9).
Description
Reset all outputs/valves
Retain current signal status for all outputs/
valves
Accept the signal status defined for the relevant
channel
Description
Retain current signal status
Accept the signal status defined by the Idle state
Reset output signal (output/valve)
Set output signal (output/valve)
Value of the analogue signal
C−19