5. Diagnostics and error handling
Error numbers of error class 2
No.
Handheld display
0
[No error]
1
[General diagnosis]
2
[Short circuit]
3
[Wire fracture/idling cur
rent I/O]
4
[Short circuit in actuator
supply]
5
[Undervoltage in power
supply]
6 ... 8
Reserved
9
[Lower limit exceeded]
10
[Upper limit exceeded]
11
[Short circuit valve]
12
Reserved
13
[Wire fracture (open load)]
14
[Condition counter excee
ded]
15
[Module/channel failure]
5−20
Operating status
No fault
General diagnosis (module−
specific error)
Short circuit/overload in sen
sor supply (SCS) or at output
(SCO)
Wire fracture/idling at current
input/output
Failure of load voltage supply
due to short circuit/overload
(on output side)
Undervoltage in power supply
(on input side)
Fall below rated range
Rated range exceeded
Short circuit at valve
Wire fracture at valve (open
load)
Limit value of the condition
counter exceeded
Module/channel failed
Eliminating faults
See manual for the relevant
module
Eliminate short circuit/over
load (see manual for the spe
cific module)
Check and, if necessary, re
place the cable and connec
ted sensors/actuators.
Check connected actuators
as well as their connections
Eliminate undervoltage at
system supply or additional
supply (see Tab. 3/4 for pin
assignment)
Check signal area and para
meterised limit
Check signal area and para
meterised limit
Check valve and pneumatic
interface
Check valve and pneumatic
interface
Set or delete the limit value of
the condition counter by para
meterising
Check module (function/in
stallation), replace if neces
sary