C445 Profibus Bit Mapping Parameters; Table 123. Bit Mapping Parameters For Cyclic/Acyclic Writeable Parameters; Table 124. Fieldbus Motor Control Bits; Table 125. Bit Mapping Parameters For Cyclic/Acyclic Readable Parameters - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

C445 PROFIBUS Bit Mapping Parameters

C445 has option of mapping individual bits in input/output
modules. Below are the bits available for bit mapping.
C445 PROFIBUS Cyclic/Acyclic Writable Parameters
Table 123. Bit Mapping Parameters for Cyclic/Acyclic
Writeable Parameters
Bit Description
Run 1
Run 2
Reserved
Fault Reset
Reserved
Test Trip
Reserved
Reserved
BCM Field Output control0
BCM Field Output control1
BCM Field Output control2
BCM Field Output control3
Note: For more information about any of the parameters
listed above, refer to System Configuration and
Commissioning on Page 47 or Appendix E.

Table 124. Fieldbus Motor Control Bits

Bit Position
Bit Description
Bit 0
Run 1
Bit 1
Run 2
Bit 2
Reserved
Bit 3
Fault Reset
Bit 4
Reserved
Bit 5
Test Trip
Bit 6
Reserved
Bit 7
Reserved
Parameter Description
Fieldbus Motor Control
Fieldbus Motor Control
Fieldbus Motor Control
Fieldbus Motor Control
Fieldbus Motor Control
Fieldbus Motor Control
Fieldbus Motor Control
Fieldbus Motor Control
BCM Field Output control
BCM Field Output control
BCM Field Output control
BCM Field Output control
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix C—Optional Communication Cards
C445 PROFIBUS Cyclic/Acyclic Readable Parameters
Table 125. Bit Mapping Parameters for Cyclic/Acyclic
Readable Parameters
Bit Description
Running 1
Running 2
Remote Enabled
Faulted
Warning
Inhibited
Ready
Up to Speed
FIELD INPUT 1
FIELD INPUT 2
FIELD INPUT 3
FIELD INPUT 4
System Services is one of the selections for an output
data word. The following are decimal values that when
sent to the C445 with the System Services word
cause the C445 to perform the designated function:
0: No Active Service
1: Clear Fault Queue
2: Clear Trip Snapshot
3: Test Trip
4: Re-pair external modules
5: Factory Reset
6: Soft Reset
7: Reset Fault
8: Proof Test
BCM Field Output Control Word is one of the
selections for an output data word. The following are
the bits that control the 3 outputs on the Base Control
Module:
Bit 0: Output 1
Bit 1: Output 2
Bit 2: Output 3 (if a Base Control Module with the
latching relay option is being used, this bit is
used to Set this output)
Bit 3: This bit is only used when a BCM with the
latching relay option is used. This bit resets the
latching relay output.
Parameter Description
BCM Status Word
BCM Status Word
BCM Status Word
BCM Status Word
BCM Status Word
BCM Status Word
BCM Status Word
BCM Status Word
Digital Input Status of BUI
Digital Input Status of BUI
Digital Input Status of BUI
Digital Input Status of BUI
233