Table 101. Dynamic Input Assembly Instance Parameters - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

C445 supports following parameters as a member of dynamic input assembly instance.

Table 101. Dynamic Input Assembly Instance Parameters

Value
Parameter Name
0
Assembly Terminator
1
Packed Device status (See Control Supervisor Object)
2
Motor Current Phase A - Scaled
3
Motor Current Phase B - Scaled
4
Motor Current Phase C - Scaled
5
Motor Current Average - Scaled
6
Line Voltage LL Phases AB
7
Line Voltage LL Phases BC
8
Line Voltage LL Phases CA
9
Line Voltage LL Average
10
Total Watts for all three phases
11
Line V Unbalance Percent
12
Motor Current Average Percent FLA
13
Apparent Power Factor
14
GF High Resistance - RMS
15
Line Frequency - Scaled
16
Thermal memory Percent
17
Signal Status Bits
18
Warning Status Bits
19
BCM Digital Input Status
Table 102. Motor Info Object—Class 0x9B (155)
Class Services
Service
Code
Service Name
0x0E
Get Attribute Single
Instance Services
Service
Code
Service Name
0x0E
Get Attribute Single
0x10
Set Attribute Single
Class Attributes
Sr. No.
Attribute ID
Access Rule Data Type
1
1 (0x1)
Get
2
2 (0x2)
Get
3
3 (0x3)
Get
Instance Attributes
Sr. No.
Attribute ID
Access
1
1 (0x1)
Get/Set
2
2 (0x2)
Get/Set
3
3 (0x3)
Get/Set
4
4 (0x4)
Get/Set
Name
UINT
Revision
UINT
Max Instance
UINT
Number of Instances
Data Type
Attribute Name
UINT
Rated Voltage
UDINT
Motor Rated Hp Motor1 (Scaled by 100)
UDINT
Motor Rated Hp Motor2 (Scaled by 100)
UDINT
Motor Rated Watts Motor1
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix C—Optional Communication Cards
Description
D_IN_ASM_TERMINATOR
C445_DEVICE_STATUS
MOTOR_I_A_SCALED
MOTOR_I_B_SCALED
MOTOR_I_C_SCALED
MOTOR_I_AVE_SCALED
LINE_V_LL_AB_RMS
LINE_V_LL_BC_RMS
LINE_V_LL_CA_RMS
LINE_V_LL_AVE_RMS
POWER_WATTS
LINE_V_UNBALANCE_PERC
MOTOR_I_AVE_PERCENT_FLA
POWER_PF_APPARENT
MOTOR_GF_I_HR_RMS
LINE_FREQ
STATUS_OVLD_THERMAL_MEM_PERCENT
STATUS_SIGNAL_BITS
STATUS_WARNING_BITS
LOGIC_INPUT_STATE_BITFIELD
Attribute Description
Revision of this object
Maximum instance number of an object currently created
in this class level of the device.
Number of object instances currently created at this class
level of the device.
Attribute Description
Motor rated voltage
Motor Rated Hp Run1
Motor Rated Hp Run2
Motor Rated Watts Run1
207

Advertisement

Table of Contents
loading

Table of Contents