Appendix D—Modbus Register Map
Table 127. C445 Modbus Register Map, continued
Register
Name
1055
Power Factor Deviation Trip
Level High Scaled
1056
Power Factor Deviation Trip
Level Low Scaled
1057
Power Factor Deviation
Alarm Level High Scaled
1058
Power Factor Deviation
Alarm Level Low Scaled
1059
Power Factor Deviation Trip
Delay
1060
Residual GF Trip Level
Scaled
282
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Attribute
Description
SINT16 RW NV
PF Deviation Trip Level High - The Power Factor Deviation protection
monitors the PF (supply side) of the load and will trip the motor if the
Default: 10000
measured deviation from rated exceeds the set threshold. The high
Range: -10000 to 10000
power factor protection is active when the motor is in the running state if
Units: 0.01%
enabled.
Config CRC
Admin Lock
USB Lock
Backup Mem
SINT16 RW NV
PF Deviation Trip Level - The Power Factor Deviation protection monitors
the PF (supply side) of the load and will trip the motor if the measured
Default: 0
deviation from rated exceeds the set threshold.
Range: -10000 to 10000
Units: 0.01%
Config CRC
Admin Lock
USB Lock
Backup Mem
SINT16 RW NV
Power Factor Deviation Alarm Level High - If the Power Factor rises
above this level, following the Alarm Delay Time in the Protections/
Default: 10000
General category, a warning is generated.
Range: -10000 to 10000
Units: 0.01%
Config CRC
Admin Lock
USB Lock
Backup Mem
SINT16 RW NV
Power Factor Deviation Alarm Level Low - If the Power Factor drops
below this level, and following the Alarm Delay Time in the Protections/
Default: 0
General category, a warning is generated.
Range: -10000 to 10000
Units: 0.01%
Config CRC
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
PF Deviation Trip Delay time is the time delay from when a Power Factor
trip condition exists to when the motor is tripped.
Default: 20
Range: 1 to 60
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
Residual Ground Fault Trip Level is the value that will generate a trip of
the motor following the Residual Ground Fault Trip Delay time. Scaled by
Default: 101
parameter "I Scale Factor".
Range: 1 to 65535 (RW)
Units: scaled A
Config CRC
Admin Lock
USB Lock
Backup Mem