Table 72. Measurement Module Specifications

Description
3 Phase Voltage input U12, U23,
U31 RMS
3 Phase Current input I1, I2, I3
RMS

Table 73. Measurement Module Frame Breaks

Frame
Size
Current Range
45 mm
0.3–2.4 Amp
45 mm
1–5 Amp
45 mm
4–32 Amp
45 mm
6–45 Amp
55 mm
N.A. 9-68 Amp
1
IEC 9-72 Amp
90 mm
11–90 Amp
90 mm
17–136 Amp
Notes
1
Use only insulated conductors.Conductor outer diameter vary with insulation type.
Refer to aperture diameter for sizing.
2
Linear to 1.2 FLA over the range of 20–80 Hz. Linear to 7 .2x FLA over 47–63 Hz range.

Table 74. EMC Emissions

Description
Radiated Emissions
Conducted Emissions
Specification
Input ratings: 110–690 Vac (94–759 Vac)
Grounded, Floating, and High-Resistance Ground Distribution systems supported.
4160 Vac with PT Ratios between 35:1 and 6:1
Connector: Removable screw terminal
U
: See Table 80.
imp
Line Frequency: 20~80 Hz
Depending on Measurement Module range
Current as % of rated FLA
0~720% max rated FLA
Supported
Aperture
Conductor NA
Dia. (mm)
600 V
1
7.8
6 AWG
7.8
6 AWG
7.8
6 AWG
7.8
6 AWG
10.5
3 AWG
15.8
2/0 AWG
15.8
2/0 AWG
Specification
EN 55011 (CISPIR 11) Group 1, Class A, ISM Equipment for Industrial, Scientific,
and Medical Equipment. 30 MHz to 1000 Mhz
The ferrite bead needs to be applied to meet requirements.
Bead should go over L1 and L2 terminals only.
IEN 55011 (CISPIR 11) Group 1, Class A, ISM Equipment for Industrial, Scientific,
and Medical Equipment. 0.15 MHz to 30 MHz.
The ferrite bead needs to be applied to meet requirements.
Bead should go over L1 and L2 terminals only.
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix A—Technical Data and Specifications
Supported
Conductor EMEA
690 V
1
Frequency Range
2
16 mm
20–80 Hz
2
2
16 mm
20–80 Hz
2
2
16 mm
20–80 Hz
2
2
16 mm
20–80 Hz
2
2
25 mm
20–80 Hz
2
2
70 mm
20–80 Hz
2
2
70 mm
20–80 Hz
2
167