Appendix D—Modbus Register Map
Table 127. C445 Modbus Register Map, continued
Register
Name
313
Active Warning
314
Active Inhibit
315
Configuration Inhibit
Reason
238
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Attribute
Description
UINT16 RO
Current Active Warning, continued
Enum
UINT16 RO
Current Active Inhibit
Enum
UINT8 RO
The reason for an active inhibit due to an incorrect or out-of-range
configuration parameter.
Enum
Value
25
Real Time Clock requires setting (has not been set)
26
RTC Battery Low. Replacement is recommended
27
Device ambient temperature high
28
MM high ambient temperature
29
UI high ambient temperature
30
Option card high ambient temperature
Value
0
No inhibits
1
Incorrect configuration. See configuration inhibit reason
2
A soft reset is required
3
Backspin prevention
4
Under voltage restart timer active
5
Control voltage is low
6
Under voltage condition
7
Voltage unbalance
8
Starts per hour limit has been exceeded
9
Over voltage condition
Value
0
No active inhibits
1
Local and Remote motor control sources both point to
Fieldwire
2
Local motor control source is set to User Interface but the
User Interface type does not match
3
One or more enabled protection features requires a voltage
option card in the Measurement Module
4
One or more enabled protection features requires a PTC
(Temperature) option card in the Measurement Module
5
Selected operational mode is incompatible with 3wire cfg
fieldwire as local control
6
Cannot choose fieldwire as the feedback source when the
fieldwire is used as a local / remote source with the
selected starter
7
UI Custom Overlay - Multiple buttons assigned to same
function
8
UI Custom Overlay - Multiple button LEDs assigned to the
same function
9
UI Custom Overlay - Multiple status LEDs assigned to the
same function
10
Selected operational mode is incompatible with the
connected UI
11
The General Purpose I/O operational mode does not use
fieldwire as a control source
Description
Description
Description