Appendix D—Modbus Register Map
Table 127. C445 Modbus Register Map, continued
Register
Name
716
Q2 Function Select
252
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Attribute
Description
UINT16 RW NV
Output Function Select for General Purpose Output 2. Available when this
output is not used by the Operation Mode. Default = none, If used by the
Default: 55
Application Mode = Reserved. A soft reset is required after modifying this
Enum
parameter, continued.
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Value
18
Tripped Status Bits - Instantaneous over current
19
Tripped Status Bits - Current unbalance
20
Tripped Status Bits - Current phase loss
21
Tripped Status Bits - Residual ground fault
22
Motor Control Status - Motor at speed
23
Motor Control Status - Ready
24
Motor Control Status - Inhibited
25
Motor Control Status - Warning
26
Motor Control Status - Faulted
27
Motor Control Status - Remote enabled
28
Motor Control Status - Running 2
29
Motor Control Status - Running 1
30
Warning Status Bits - PTC
31
Warning Status Bits - Phase rotation mismatch
32
Warning Status Bits - Stall
33
Warning Status Bits - Overload
34
Warning Status Bits - Starts limit exceeded
35
Warning Status Bits - Low power
36
Warning Status Bits - High power
37
Warning Status Bits - Under current
38
Warning Status Bits - Frequency deviation slow
39
Warning Status Bits - Frequency deviation fast
40
Warning Status Bits - Voltage unbalance
41
Warning Status Bits - Voltage phase loss
42
Warning Status Bits - Power factor deviation
43
Warning Status Bits - Jam
44
Warning Status Bits - Instantaneous over current
45
Warning Status Bits - Current unbalance
46
Warning Status Bits - Current phase loss
47
Warning Status Bits - Residual ground fault
48
Warning Status Bits - External ground fault
49
Warning Status Bits - Over voltage
50
Warning Status Bits - Under voltage
51
Tripped Status Bits - Under voltage
52
Tripped Status Bits - Over voltage
53
Tripped Status Bits - External ground fault
54
Base Control Module Field Output control word - Bit 0
55
Base Control Module Field Output control word - Bit 1
56
Base Control Module Field Output control word - Bit 2
57
Base Control Module Field Output control word - Bit 3
65535