Table 127. C445 Modbus Register Map, continued
Register
Name
711
Local Control Source
712
Remote Control Source
713
Feedback Signal Source
Select
714
Local/Remote PowerUp
Behavior
Attribute
UINT8 RW NV
Default: 0
Enum
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Default: 1
Enum
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Default: 0
Enum
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Default: 2
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix D—Modbus Register Map
Description
Allows the user to select the local source of control. The default if a User
Interface is included is "Auto Detect User Interface". Other choices are
no local control and fieldwire control.
Value
0
Auto detect User Interface
1
No local control
2
User Interface local control
3
Fieldwire local control
Remote Control Source Select. Selects the control source when in "Auto"
mode.
Value
0
No remote control source
1
Fieldbus is remote control source
2
Fieldwire is remote control source
Selects the source of the digital inputs used for the feedback signals for
certain operation modes. The operation modes that require digital input
feedback are: Solenoid, MCCB Actuation and Contactor Feeder. This
parameter allows the user to select where the inputs are wired to the
C445. To the Base Control Module, the User Interface or to a controller
where they are sent to the C445 via a communication network. For all
three locations these input feedback signals may be wired, the actual
input or bit is pre-defined for each as follows. Solenoid Operation
Mode: 1. Base Control Module: Input 2 (open), Input 3 (closed)
2. CUI: Input 2 (open), Input 3 (closed) 3. Input Register 602 from a
controller: Bit 1 (open) and Bit 2 (closed) Contactor Feeder Operation
Mode: 1. Base Control Module: Input 2 (AUX On) 2. CUI: Input 2 (AUX On)
3. Input Register 602 from a controller: Bit 1 (AUX On) MCCB Feeder
Operation Mode: 1. Base Control Module: Input 2 (CB On), Input 3 (CB
Alarm) 2. CUI: Input 2 (CB On), Input 3 (CB Alarm) 3. Input Register 602
from a controller: Bit 1 (CB On), Bit 2 (CB Alarm)
Value
0
No feedback signals
1
Feedback signals connected to User Interface inputs
2
Feedback signals connected to Base Control Module field
wiring inputs
3
Feedback signals provided by network
Select the Local/Remote mode the Base Control Module will power up in.
Selections: 0: Local control is active control on power up, 1: Remote
control is active control on power up, 2: Hold last control state on
power up.
Value
0
Local control is active control on power-up
1
Remote control is active control on power-up
2
Hold last control state on power-up
Description
Description
Description
Description
249