Appendix D—Modbus Register Map
Table 127. C445 Modbus Register Map, continued
Register
Name
6037
IP Conflict Detection Status
6038
IP Conflict Detection
Conflicted Status
6039
IP Conflict Detection
Conflicted MAC
6048
Ethernet MAC Address
6052
Profibus Modbus Timeout
6053
Set UI Local Password
6055
UI Local Login
7000
Minimum FLA (Nominal
Current) Scaled
7001
Maximum FLA (Nominal
Current) Scaled
298
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Attribute
Description
UINT8 RO
Address Conflict Detection State. This is read only. 0 = no conflict
detected, 1 = conflict detected - defending, 2 = conflict detected -
Enum
retreated.
UINT8 RW NV
Address Conflict Detection Status. The state of ACD activity when the last
conflict was detected.
Default: 0
Range: 0 to 0
UINT8 RW NV
Address Conflict Detection conflicted device MAC address. The source
MAC address from the header of the received Ethernet packet which was
Array size: 6
sent by a device reporting a conflict. All Ethernet devices have a unique
Default: 0
MAC address so by reporting the MAC address of the device containing
Range: 0 to 0
the duplicate IP address allows the issue to be resolved in a timely
manner.
Array of 3 registers
UINT8 RO
Unique MAC Address assigned to this device.
Array size: 6
Array of 3 registers
UINT16 RW NV
The time before Modbus communications are considered lost. Every valid
message received will reset this timer. The timeout is based on
Default: 2000
milliseconds. When this timer expires, communication loss behavior will
Units: ms
be triggered. A value of zero (0) will disable the communication timeout.
Backup Mem
UINT32 RW
Set UI local password (0x00000000 means no password)
Default: 0x00000000
Range: 0 to 9999
Admin Lock
USB Lock
Backup Mem
UINT32 RW
Log in with UI local password
Range: 0 to 9999
UINT16 RO
Minimum Setting allowed for Full Load Amperes, Scaled (Nominal
Current). The minimum range is based on the measurement module used.
Default: 1
Scaled by parameter "I Scale Factor".
Units: scaled A
UINT16 RO
Maximum Setting allowed for Full Load Amperes, Scaled (Nominal
Current). The max range is based on the Measurement Module used.
Default: 65535
Scaled by parameter "I Scale Factor".
Units: scaled A
Value
0
No conflict detected
1
Conflict detected - defending
2
Conflict detected - retreated
Description