Table 28. Current Based Protections - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Current Based Protection Parameters

Table 28. Current Based Protections

Fault
Code
Protection
Action
19
Thermal Overload
Fault Trip
Fault Warning
7
Instantaneous
Fault Trip
Overcurrent
Fault Warning
8
Jam
Fault Trip
Fault Warning
20
Stall
Fault Trip
14
Undercurrent
Fault Trip
Fault Warning
6
Current Unbalance
Fault Trip
Fault Warning
10
Phase Loss
Fault Trip
4
Ground Fault (earth) Fault Trip
Note
1
ABC wiring recommended.
Fault Action
Default
Status
Units
Enabled
Amps
Disabled %
Disabled % FLA
Disabled % FLA
Disabled % FLA
Disabled % FLA
Disabled % FLA
Disabled % FLA
Disabled % FLA
Enabled
%
Disabled %
Enabled
%
Enabled
Amps
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Motor FLA
Note
Min.
Max.
C445MA2P4...
0.3
2.4
C445MA005...
1
5
C445MA032...
4
32
C445MA045...
5.6
45
C445MB072...
9
72
C445MC090...
11
90
C445MC136...
17
136
C445...ext
ext
800
1
100
50
400
50
400
50
400
50
400
50
400
10
90
10
90
1
60
1
60
60
60
C445MA2P4...
0.12
2.4
C445MA005...
0.25
5
9.6
C445MA032...
1
1
C445MA045...
1
1
13.5
C445MB072...
3
1
21.6
C445MC090...
3
27
C445MC136...
34
40.8
C445...ext
30% of
50% of
CT
CT
Primary
Primary
Chapter 6—Motor Protection
Delay (Seconds)
Default
Min.
Max.
0.3
Class 5
Class 40
1
4
5.6
9
11
17
ext
90
0
0
400
0.001
2
400
0.2
5
400
1
60
400
0.2
5
200
0
0
50
1
60
50
0.2
5
15
1
60
15
0.2
5
60
2
2
1
1
60
3
3
3
3
3
34
50% of CT
Primary
Default
Class 5
0
2
2
10
2
0
20
2
15
2
2
5
127