Table 127. C445 Modbus Register Map, continued
Register
Name
1302
Snap Shot Day
1303
Snap Shot Hour
1304
Snap Shot Minute
1305
Snap Shot Second
1306
Snap Shot Trip Reason
Attribute
UINT8 RO
Default: 0
Backup Mem
UINT8 RO
Default: 0
Backup Mem
UINT8 RO
Default: 0
Backup Mem
UINT8 RO
Default: 0
Backup Mem
UINT16 RO
Default: 0
Enum
Backup Mem
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix D—Modbus Register Map
Description
Fault Snap Shot Log Day. The Day from the time stamp information when
the last fault occurred.
Fault Snap Shot Log Hour. The Hour from the time stamp information
when the last fault occurred.
Fault Snap Shot Log Minute.The Minute from the time stamp information
when the last fault occurred.
Fault Snap Shot Log Second. The Seconds from the time stamp
information when the last fault occurred.
The fault that caused the last trip.
Value
0
No Faults
1
Under voltage
2
Over voltage
3
External GF
4
Residual GF
5
Current phase loss
6
Current unbalance
7
Instantaneous over current
8
Jam
9
PF Deviation
10
Voltage phase loss
11
Voltage unbalance
12
Frequency deviation fast
13
Frequency deviation slow
14
Under current
15
High power
16
Low power
17
Contactor failure
18
Starts limit exceeded
19
Overload
20
Stall
21
Phase rotation mismatch
22
PTC - See PTC State for details
23
Under voltage restart
24
Measurement Module fault
25
Communication loss on active fieldbus
26
Measurement Module not available or communication loss
with the module
27
User Interface not available or communication loss with the
module
28
Test trip was triggered
29
Option Card not available or communication loss with the
module
Description