Chapter 5—System Configuration and Operation
General Field Output Control Word
The general purpose output can be activated/de-activated
over a fieldbus network.
Output Control Bits
Bit 0
0 = de-activate the Output 1
1= activate the Output 1
Bit 1
0 = de-activate the Output 2
1= activate the Output 2
Bit 2
0 = de-activate the Output 3
1= activate/set the Output 3
Bit 3
0 = No action
1= Output 3 latching relay reset
Note: The Outputs can be configured to be controlled
by any of the bits of this control word. The above
designations are showing the most common usage.
118
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
General Input Status Word
The general purpose inputs status over a fieldbus network.
Input Status Bits
Bit 0
0 = base unit input 1 off
1= base unit input 1 on
Bit 1
0 = base unit input 2 off
1= base unit input 2 on
Bit 2
0 = base unit input 3 off
1= base unit input 3 on
Bit 3
0 = base unit input 4 on
1= base unit input 4 off
Bit 4
0 = control user interface input 1 off
1= control user interface input 1 on
Bit 5
0 = control user interface input 2 off
1= control user interface input 2 on
Bit 6
0 = control user interface input 3 off
1= control user interface input 3 on
Bit 7
0 = control user interface input 4 off
1= control user interface input 4 on