Table 127. C445 Modbus Register Map, continued
Register
Name
1084
Start Threshold Percent
1085
Stop Threshold Percent
1086
Transition Threshold
Percent
1200
Fault Queue - Event Order
Attribute
UINT8 RW NV
Default: 30
Range: 1 to 100
Units: %
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Default: 5
Range: 1 to 50
Units: %
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Default: 115
Range: 25 to 200
Units: %
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT16 RO
Array size: 10
Enum
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix D—Modbus Register Map
Description
The C445 recognizes a motor Start when it measures motor current
exceeding 30% of the FLA setting by default.
A motor Stop is recognized when the current falls below 5% of the FLA
setting by default.
Motor Transition to Run Threshold Percent.
A List of the Last 10 Faults Shown in the Order They Occurred. Duplicates
are allowed and the most recent is at the top.
Value
0
No Faults
1
Under voltage
2
Over voltage
3
External GF
4
Residual GF
5
Current phase loss
6
Current unbalance
7
Instantaneous over current
8
Jam
9
PF Deviation
10
Voltage phase loss
11
Voltage unbalance
12
Frequency deviation fast
13
Frequency deviation slow
14
Under current
15
High power
16
Low power
17
Contactor failure
18
Starts limit exceeded
19
Overload
Description
287