Advertisement

Appendix D—Modbus Register Map

C445 Modbus Register Map

Table 127. C445 Modbus Register Map

Register
Name
300
Motor Control Status
301
I Phase A (L1) Scaled
302
I Phase B (L2) Scaled
303
I Phase C (L3) Scaled
304
Avg Current Scaled
305
I Scale Factor
306
Current Unbalance
307
GF Current RMS Scaled
308
Thermal Capacity
309
Time to Trip Overload
310
Remaining Thermal
Capacity
311
Time to Reset Overload
Attribute
BYTE RO
Bitfield
UINT16 RO
Units: scaled A
UINT16 RO
Units: scaled A
UINT16 RO
Units: scaled A
UINT16 RO
Units: scaled A
UINT16 RO
UINT8 RO
Units: %
UINT16 RO
Units: scaled A
UINT8 RO
Default: 0
Units: %
UINT16 RO
Units: seconds
UINT8 RO
Units: %
UINT16 RO
Units: seconds
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix D—Modbus Register Map
Description
Present Motor Control Status Bits (Running1, Running2, Remote, Tripped,
Warned).
Bit
Description
0
Running 1
1
Running 2
2
Remote enabled
3
Faulted
4
Warning
5
Inhibited
6
Ready
7
Motor at speed
Phase A (L1) Motor Current Scaled. Scaled by parameter "I Scale
Factor".
Phase B (L2) Motor Current Scaled. Scaled by parameter "I Scale
Factor".
Phase C (L3) Motor Current Scaled. Scaled by parameter "I Scale
Factor".
Average motor Current Scaled. Scaled by parameter "I Scale Factor".
This scale factor is applied to all current values monitored via a
communication network.
Motor Current Unbalance Percent
Motor Residual Ground Fault scaled current RMS. Scaled by parameter "I
Scale Factor".
Thermal Capacity in Percent - An overload trip occurs when the Thermal
Capacity reaches 100%.
Estimated Time for Overload to Reach Trip Threshold (100% Thermal
Memory)
Thermal Capacity (Percent) Remaining to Trip
Time for overload to reach reset threshold. The Thermal Memory must
drop below 75% (default value) before a reset is allowed.
Coil
4785
4786
4787
4788
4789
4790
4791
4792
235