Two Speed Dahlander Operation Mode
The Two Speed Dahlander motor starter operation mode
accepts OFF/SLOW/FAST commands to control two speed
motor applications. A RUN SLOW command will activate
Output 1(slow). A RUN FAST command will activate Output
3(net). Then after the Network Contactor Delay time expires,
Output 2(fast) activates starting the motor on the fast
winding. A STOP command de-activates all 3 outputs.
When transitioning from fast R slow, the C445 will
de-activate both Output 2(fast) and Output 3(net) and will
delay activating Output 1(slow) until the Control Switching
Time Delay expires, allowing the motor time to slow down
before transitioning to the slow speed.
The C445 will issue a control fault when:
The RUN SLOW or RUN FAST command is active and
phase voltage is present and no phase current is detected.
A STOP command is active and current is detected.
Note: Even with the control fault disabled, after de-activating
the present speed, the C445 will NOT transition to the
new speed until current readings decrease to zero.
Outputs 1, 2 and 3 will be de-activated anytime the C445
experiences a fault/inhibit condition.
Output 1 – SLOW STARTER coil (NO)
Output 2 – FAST STARTER coil (NO)
Output 3 – NET STARTER coil (NO)
The AtRef (At Reference) bit in the Motor Control Status
register is set based on the following two conditions. At
Reference signals that the motor is up to speed.
1.
If motor current first exceeds 115% of the active
overload FLA rating and then decreases back below
115% of the active overload FLA rating, it is determined
the motor has come up to speed and the AtRef bit will
be set.
2.
If motor current exceeds 30% of the active overload FLA
rating and remains until after the Motor State Transition
to Run Delay from Start time expires the motor is
determined to be up to speed and the AtRef bit will be
set. This time delay parameter can be found in the
General Protections category in the Power Xpert
inControl Software Tool.
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Chapter 5—System Configuration and Operation
Figure 105. Timing Diagram for the Two Speed Dahlander
Operation Mode
Timing Diagram
Control Fault Delay
SLOW
Settle Time
NET
FAST
Speed Transition Delay