Table 127. C445 Modbus Register Map, continued
Register
Name
1073
Auto Reset Types
1075
Auto Reset Delay
1076
Reset on Powerup
Attribute
BYTE RW NV
Array size: 4
Default: 0
Bitfield
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
Default: 180
Range: 0 to 3600
Units: seconds
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
BOOL RW NV
Default: FALSE
Config CRC
Admin Lock
USB Lock
Backup Mem
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Appendix D—Modbus Register Map
Description
Select the protections that are to auto-reset if Auto Reset Enable is
enabled. Each protection type is a bit.
Bit
Description
0
Under voltage
1
Over voltage
2
External ground fault
3
Residual ground fault
4
Current phase loss
5
Current unbalance
6
Instantaneous over current
7
Jam
8
Power factor deviation
9
Voltage phase loss
10
Voltage unbalance
11
Frequency deviation fast
12
Frequency deviation slow
13
Under current
14
High power
15
Low power
16
Reserved
17
Starts limit exceeded
18
Overload
19
Stall
20
Phase rotation mismatch
21
PTC
22
Under voltage restart
23
Peak demand
The time delay following a fault before attempting to auto-reset that fault
condition.
If enabled, perform a fault reset on power up.
Coil
17153
17154
17155
17156
17157
17158
17159
17160
17161
17162
17163
17164
17165
17166
17167
17168
17169
17170
17171
17172
17173
17174
17175
17176
285