DC Input Option
The C445 Base Control Module with the DC Input option
allows for four isolated 24 Vdc Inputs (Option #1) or four dry
contact (relay/switches) inputs (Option #2).

Figure 44. DC Field Input Terminal

Field
1
2
3
4
5
6
7
Pin#
Circuit
Description
1
I1
DC Field Input 1
2
I2
DC Field Input 2
3
I3
DC Field Input 3
4
I4
DC Field Input 4
5
C
Common for DC Field Input
6
0V
Digital Electronics Ground
7
24V
Source for DC Field Inputs
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Chapter 3—Installation and Wiring
Wiring Option #1—Four Isolated 24 Vdc Inputs
When using option #1, no connections are made to pins 6 or 7.
Wiring Option #2—Four Dry Contact Inputs
To use this option, pin 5 is shorted directly to pin 6. Pin 7 is
connected through a switch or relay to the appropriate input.
The maximum wire length from pin 7 to the corresponding
input is 10m.
DC Field Input wiring is accomplished with a 7-pin, 5.00 mm
pitch, removable screw terminal plug.
Note: When using Option #2, all wiring must meet PELV
requirements.