Input Instance 110 (0x6E): Status, Current, Voltage, Trip, continued
Length = 22 Bytes
Byte
Size
Offset
(bytes)
Name
8
4
Trip Reason
12
2
Current Average
14
2
Voltage
L1-L2
16
2
Voltage
L2-L3
18
2
Voltage
L3-L1
20
2
Voltage
Average
Description
STATUS_TRIPPED_BITS
0x0000 0001 - under voltage
0x0000 0002 - over voltage
0x0000 0004 - high resistance GF
0x0000 0008 - residual GF
0x0000 0010 - current phase loss
0x0000 0020 - current unbalance
0x0000 0040 - instantaneous over current
0x0000 0080 - jam
0x0000 0100 - PF deviation
0x0000 0200 - voltage phase loss
0x0000 0400 - voltage unbalance
0x0000 0800 - freq deviation fast
0x0000 1000 - freq deviation slow
0x0000 2000 - under current
0x0000 4000 - high power
0x0000 8000 - low power
0x0001 0000 - overload
0x0002 0000 - stall
0x0004 0000 - phase rotation
0x0008 0000 - exceeds starts limit
0x0010 0000 - initialization fault
0x0020 0000 - NV memory fault
0x0040 0000 - comm loss
0x0080 0000 - comm msg error
MOTOR_I_AVE_SCALED:
Average Motor Current Scaled.
Scaled by parameter "I Scale Factor."
LINE_V_LL_AB_RMS:
Phase A RMS Voltage L1-L2 (V)
LINE_V_LL_BC_RMS:
Phase B RMS Voltage L2-L3 (V)
LINE_V_LL_CA_RMS:
Phase C RMS Voltage L3-L1 (V)
LINE_V_LN_AVE_RMS:
Average RMS Voltage (V)
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com