Eaton Power Xpert C445 User Manual page 249

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Appendix D—Modbus Register Map
Table 127. C445 Modbus Register Map, continued
Register
Name
312
Active Fault
236
Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com
Attribute
Description
UINT16 RO
Current Active Fault
Default: 0
Enum
Value
0
No Faults
1
Under voltage
2
Over voltage
3
External GF
4
Residual GF
5
Current phase loss
6
Current unbalance
7
Instantaneous over current
8
Jam
9
PF Deviation
10
Voltage phase loss
11
Voltage unbalance
12
Frequency deviation fast
13
Frequency deviation slow
14
Under current
15
High power
16
Low power
17
Contactor failure
18
Starts limit exceeded
19
Overload
20
Stall
21
Phase rotation mismatch
22
PTC - See PTC State for details
23
Under voltage restart
24
Measurement Module fault
25
Communication loss on active fieldbus
26
Measurement Module not available or communication loss
with the module
27
User Interface not available or communication loss with the
module
28
Test trip was triggered
29
Option Card not available or communication loss with the
module
30
RTC / Backup Memory Option Board NV memory fail
31
Currently connected User Interface does not match with
what was connected before
32
Currently connected Measurement Module does not match
with what was connected before
33
Currently connected Option Card does not match with what
was connected before
34
Measurement Module firmware is incompatible
35
User Interface firmware is incompatible
36
Ethernet Option Card firmware is incompatible
37
Profi Option Card firmware is incompatible
Description

Advertisement

Table of Contents
loading

Table of Contents