Chapter 3 - Installation
Table 3-3: Alarm Relay Contact Information
Unit
Alarm relay
power
Wiring
Off
N.O.
N.C.
On
N.O.
N.C.

Mounting

45
Variable NOT in Alarm
State
Relay
Contact
Open
Closed
Closed
Open

Physical Considerations

The controller can be mounted on either a vertical or tilted panel
using the mounting kit supplied. Adequate access space must be
available at the back of the panel for installation and servicing
activities.
The controller must be installed indoors.
n
It must be panel mounted with the wiring terminals enclosed
n
within the panel.
The instrument is environmentally hardened and, when suitably
n
enclosed, can be mounted anywhere in plant or factory, on the
wall, or even on the process machine itself.
The front panel is moisture rated NEMA3R and IP54 rated and
n
can be easily upgraded to NEMA4X and IP66 for the most severe
hose-down applications. See
Procedure
for more information.
It withstands ambient temperatures 0 ~ 55 C (32 ~ 131 F) and
n
resists the effects of vibration and shock.
Overall dimensions and panel cutout requirements for mounting
n
the controller are shown in figure below. See Overall Dimensions
for more information.
The controller's mounting enclosure must be grounded according
n
to CSA standard C22.2 No. 0.4 or Factory Mutual Class No. 3820
paragraph 6.1.5.
Variable in Alarm State
Relay
Indicators
COntact
Off
Open
Closed
Off
Open
Closed
Mounting Method
Indicators
Off
On
and

Mounting