Setting The Dip Switches - Honeywell PW-6000 Installation And Configuration Manual

Intelligent controller and system
Hide thumbs Also See for PW-6000:
Table of Contents

Advertisement

PW-6000 Installation
Setting Up the PW-6000 Hardware

3.2 Setting the DIP Switches

Dual In-line Package (DIP) switches are read when the system powers up, except
where noted otherwise. The following table shows the setting options.
Table 2 PW-6000 DIP Switch Settings
S1
OFF
ON
OFF
ON
12
S2
S3
S4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
Selection
Normal Operating Mode.
When DIP switch 1 is ON, Port 0
communicates with the web browser.
Port 1 is used for RS-232/485
communications. After the panel
initialization, enable the default user
name (admin) and password (password).
The user name and password are read
dynamically; you do not need to reboot
the panel.
Use the factory default communication
parameters.
Unless the network administrator
reserves an IP address for the panel
(based on the controller board's Media
Access Control (MAC) address), the
PW-6000 uses Dynamic Host
Configuration Protocol (DHCP) to
obtain an IP address from the network
DHCP server.
When power is applied with the
switches in this position, there is a ten
second window (when LEDs 1and 2
flash alternately with LEDs 3 and 4),
during which memory is cleared if
switch 1 or switch 2 is changed to OFF.
When switch 1 or 2 is changed to OFF,
only LED 2 flashes and memory begins
to be cleared. This period of clearing
lasts several minutes. When the memory
has been cleared, the LED pattern
changes to the flashing of LEDs 1 and 4.
The panel then reboots by itself. All data
in memory is erased except the serial
number, MAC address, hardware
revision, and OEM code.
www.honeywell.com

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pw6k1ic

Table of Contents