A5:Self-Adaption Mode
Power-on self-adaption: The actuator will directly enter into self-adaption
mode after being powered up. Meanwhile, the yellow indicator on PCB blinks
(1Hz) and the actuator will be automatically full off (traveling to the bot-
tom) and then full on(traveling to the top). When the indicator stops blink-
ing, it means that the process is completed. Afterwards, the actuator will
travel to the designated position of control signal.
Manual self-adaption: Press and hold button S1 on PCB for more than 5s (See
Fig. 1) until the indicator starts blinking (1Hz) to enter into self-adaption
mode. The phenomenon will be the same as power-on self-adaption.
A6

DIP Switch Setting

DIP
Function
Setting of control/
S2-1
feedback signal
Setting of control
S2-2
signal type
Setting of control
S2-3
signal input impedance
Setting of valve
S2-4
position feedback
signal type
Setting of operating
S2-5
mode
Setting of signal
S2-6
interruption mode
Setting of self-
S2-7
adaption mode
Setting of control
S2-8
mode
S2-9
Reserved
S2-10
Speed setting
24V
ON
20%:The control/feedback signal is 4~20mA or 2~10VDC
OFF
0: The control/feedback signal is 0~20mA or 0~10VDC (factory default)
ON
II:The control signal is current type.
OFF
UI:The control signal is voltage type. (factory default)
ON
UI:The control signal is voltage type. (factory default)
OFF
II:The control signal is current type.
ON
IO:The valve position feedback signal is current type.
OFF
UO:The valve position feedback signal is voltage type. (factory default)
ON
DA: When control signal increases, actuator moves downward. When control signal decreases, actuator moves upward.
RA: When the control signal increases, the actuator moves upward. When control signal decreases, the actuator moves
OFF
downward. (factory default)
DW:When the control signal type is set as voltage or current, the actuator will automatically provide a minimum control
ON
signal if the signal cable is cut. (factory default)
UP:1)When the control signal type is set as voltage, the actuator will automatically provide a maximum control signal if
the signal cable is cut.
OFF
2)When the control signal is set as current, actuator will automatically provide a minimal signal when the signal cable
ON
DF: In power-on self-adaption mode. (factory default)
OFF
RF: In manual self-adaption mode.
ON
Floating control.
OFF
Modulating control. (factory default)
ON
High speed: 600N - 3s/mm, 1800N - 2s/mm.
OFF
Low speed: 600N - 4s/mm, 1800N - 3s/mm.(factory default)
B:Manual
Clockwise
Anticlockwise
Function Description of Setting Value