Representation Of Analog Values For Resistance-Based Sensors - Siemens SIMATIC ET 200AL Manual

Analog input module ai 4xrtd/tc 4xm12
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Representation of analog values
B.2 Representation of analog values for resistance-based sensors
B.2

Representation of analog values for resistance-based sensors

Resistance-based sensor
The following tables list the decimal and hexadecimal values (codes) of the resistance-based
sensor.
Table B- 2
Resistance-based sensor of 150 Ω and 300 Ω
Values
Dec.
Hex.
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
Note
Negative value for 2-wire connection
A negative value is possible in these constellations:
• Configured conductor compensation > sum of conductor resistance and resistance
• Short-circuit on the input and configured conductor compensation
With a negative value the value 7FFF
limit" is signaled for the channel in question.
48
Resistance-based sensor range
150 Ω
300 Ω
>176.38 Ω
>352.77 Ω
176.38 Ω
352.77 Ω
150 Ω
300 Ω
112.5 Ω
225 Ω
5.43 mΩ
10.85 mΩ
0 Ω
0 Ω
is generated. The diagnostic message "Violation of high
H
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Range
Overflow
Overrange
Nominal range
Equipment Manual, 08/2020, A5E48753535-AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7144-5kd50-0ba0

Table of Contents