Introduction To Counting And Frequency Measurement - Siemens SIMATIC CFU Commissioning Manual

Distributed i/o
Hide thumbs Also See for SIMATIC CFU:
Table of Contents

Advertisement

Operating modes and functions

5.2 Introduction to counting and frequency measurement

Settings:
● High
● Low
Substitute values
Note
Substitute values
While the selected signal level is pending on the channel for the actuator disconnection,
substitute values are also set to low level by the actuator disconnection.
Configuring an actuator shutdown
1. Open HW Config.
2. Select the CFU.
3. In the index list, double-click the "DIQ" slot.
The "Properties - DIQ..." dialog box opens.
4. In the "Parameters" tab, select the submenu "Actuator shutdown" and configure a
monitoring channel and the signal level for the shutdown.
Shutdown time
The maximum shutdown time is 10 ms.  
5.2
Introduction to counting and frequency measurement
Requirement for using the "Counter" or "Frequency measurement" operating modes
If you want to activate the "Counter" or "Frequency measurement" operating mode for DI
channels, the required submodule must be configured with the parameterization tool (see table
below).
The "Counter" or "Frequency measurement" operating mode can be selected at the following
channels depending on the CFU type:
CFU type
CFU PA
CFU DIQ
36
Required submodule
DIQ8 DC24V/0.5A, Counter
DIQ16 DC24V/0.5A, Counter
Channel for "Counter" or "Frequency measure‐
ment" operating mode
● Channel 0
● Channel 0
● Channel 1
Commissioning Manual, 08/2019, A5E39252870-AD