Festo CPX-FB6 Manual page 24

Cpx fieldbus node
Hide thumbs Also See for CPX-FB6:
Table of Contents

Advertisement

1. Installation
1-8
Setting the operating mode
You can set the operating mode of the CPX terminal with
switch element 1 of the dual DIL switch 1:
Operating mode
Remote I/O operating mode
Standard remote bus station on
the Interbus; all inputs and out-
puts are controlled by the PLC.
A possible CPX-FEC or CPX-CEC
integrated in the CPX terminal
works as a passive function
module.
Operating mode Remote Con-
troller
A CPX-FEC or CPX-CEC integrated
into the CPX terminal takes over
I/O control. This operating mode
is only useful if an FEC/CEC is in-
tegrated into the CPX terminal.
Tab. 1/1:
Setting the bus node operating mode
Note
The setting of the operating mode with the DIL switch has
priority over all other settings.
1
Setting DIL switch 1.1
1.1: OFF
(default)
1.1: ON
Festo P.BE-CPX-FB6-EN en 1207c