3.7

MSI-SD-CARD removable storage

3.7.1

Description

The system configuration of the entire MSI 400 system is stored in the MSI-SD-CARD program removable
storage. This has the advantage that the MSI 400 system does not have to be reconfigured when modules
are replaced.
The MSI-SD-CARD removable storage is an SD card that is produced and formatted specially for use in
the controller modules.
Important information
NOTICE
Ä The data stored in the MSI-SD-CARD program removable storage will be retained even if
i
the supply voltage is interrupted.
Ä When replacing a module, make sure that the program removable storage is inserted into
the appropriate controller module. Mark all of the connection lines and plug connectors on
the MSI 400 system clearly to prevent mixups.
Ä Commonly available SD cards cannot be used/inserted in MSI 400 and controller modules.
Ä The replacement of a verified user project can be recognized on the entry of the diagnostic
number 24230000.
Ä After the user project is transfered to the SD card and the user project has been replaced by
replacing the SD card, the correct function of the safety application must be checked.
Ä Make sure that the SD card cannot be replaced by authorized personnel.
3.7.2

Files on the removable storage

The following table explains the significance of the files on the removable storage MSI-SD-CARD.
Tab. 3.10:
Files on MSI-SD-CARD
File name
config.yaml
HISTORY.CSV
Leuze electronic
WARNING
Function
Basic configuration of the
communication (device
name, TCP/IP configuration
etc.)
Non-volatile storage of dia-
gnostics and error entries
Reading...
... at device start.
and
... in MSI.designer in the
configuration dialog of the
controller (Properties
docking window) if you click
on the Control configura-
tion | Send.
... from MSI.designer for
the Diagnostics view.
MSI 400
Product description
Writing...
... with the basic data be-
fore the initial delivery.
and
... in MSI.designer in the
configuration dialog of the
controller (Properties
docking window) if you click
on the Control configura-
tion | Send.
and
... when sending new data
from a PLC via
PROFINET IO or EtherNet/
IP.
... for a new diagnostic or
error event.
and
... in the Diagnostics view
of MSI.designer click on the
2)
Delete button
.