12.3

Data sheet

12.3.1 Controller module

Tab. 12.7:
MSI 410 and MSI 420/430 data sheet
Safety Integrity Level
1
SIL claim limit
Category
Performance Level
PFHd (average probability of a
hazardous-causing failure per
hour)
T
(usage time)
M
Protection class
Protection type
Ambient temperature during op-
eration
Storage temperature
Humidity
Fatigue strength
Shock resistance
• Continuous shock
• Brief shock
Electromagnetic compatibility
Data interface
Configuration interface 1
Configuration interface 2
Plug-in terminal blocks and
connection data
Single-wire or fine-strand
Fine-strand with ferrules
Conductor size AWG
(use copper cables only)
Maximum tightening torque
Stripping length
Dimensions (W × H × L)
Weight
Power supply for the system (A1, A2)
Supply voltage
Leuze electronic
MSI 410 / MSI 420/430
SIL3 (IEC 61508)
SILCL3 (EN 62061)
Category 4 (EN ISO 13849‑1)
1
PL e (EN ISO 13849‑1)
20 years (EN ISO 13849)
III (EN 61140)
IP 20 (EN 60529)
-25 to +65°C
-25 to +70 °C
10 to 95%, non-condensing
5 ... 150 Hz (EN 60068‑2‑6)
10 g, 16 ms (EN 60068-2-29)
30 g, 11 ms (EN 60068-2-27)
Class A (EN 61000-6-2, EN 55011)
Internal safety bus
USB mini
RJ 45
Screw terminal
1 x 0.2 ... 2.5 mm
2 x 0.2 ... 1.0 mm
1 × 0.25 ... 2.5 mm
2 × 0.25 ... 1.0 mm
26...14
0.5 ... 0.6 Nm (5 ... 7
lbf-in)
7 mm
45 × 96.6 × 121 mm
290 g (± 5%)
24 V DC (16.8 to 30 V DC)
Spring-loaded ter-
minal
2
or
2 x 0.2 ... 1.5 mm
2
2
or
2 × 0.25 ... 1.5 mm
2
24 to 16
45 × 107 × 121 mm
290 g (± 5%)
MSI 400
Technical data
2
2
81

Hide quick links:

Advertisement

Table of Contents
loading