Safe Input/Output Expansion Module - Leuze electronic MSI 400 Operating Instructions Manual

Integrating safety sensors
Hide thumbs Also See for MSI 400:
Table of Contents

Advertisement

12.3.2 Safe input/output expansion module

Tab. 12.8:
MSI-EM-IO84 data sheet
T
(usage time)
M
Protection class
Protection type
Ambient temperature during op-
eration
Storage temperature
Humidity
Fatigue strength
Shock resistance
• Continuous shock
• Brief shock
Electromagnetic compatibility
Power consumption via internal
safety bus without currents at X1,
X2
Data interface
Plug-in terminal blocks and
connection data
Single-wire or fine-strand
Fine-strand with ferrules
as per EN 46228
Conductor size AWG
(use copper cables only)
Maximum tightening torque
Stripping length
Dimensions (W × H × L)
Weight
Output supply (A1, A2)
Supply voltage
Type of supply voltage
Power consumption
Switch-on time
Short-circuit protective device
Input circuit (I1–I8)
Input voltage HIGH
Input voltage LOW
Leuze electronic
MSI-EM-IO84
20 years (EN ISO 13849)
III (EN 61140)
Terminals: IP 20 (EN 60529)
Housing: IP 40 (EN 60529)
-25 ... +65 °C
-25 ... +70 °C
10 to 95 %, non-condensing
5 ... 150 Hz (EN 60068‑2‑6)
10 g, 16 ms (EN 60068-2-29)
30 g, 11 ms (EN 60068-2-27)
Class A (EN 61000‑6‑2, EN 55011)
max. 1.1 W
Internal safety bus
Screw terminal
2
1 x 0.2 ... 2.5 mm
or
2
2 x 0.2 ... 1.0 mm
1 × 0.25 ... 2.5 mm² or
2 × 0.25 ... 1.0 mm²
26 to 14
0.5 ... 0.6 Nm (5 ... 7
lbf-in)
7 mm
22.5 × 96.5 × 121 mm
164 g (± 5%)
24 V DC (16.8 to 30 V DC)
PELV or SELV
The current for the powerpack must be limited to
a maximum of 4 A – either by the powerpack it-
self or by a fuse.
1W
Max. 18 s
4 A gG (with tripping characteristic B or C)
13 to 30 V DC
-5 to +5 V DC
MSI 400
1
Spring-loaded ter-
minal
2
2 x 0.2 ... 1.5 mm
2 × 0.25 ... 1.5 mm²
24 to 16
22.5 × 107 × 121 mm
164 g (± 5%)
Technical data