3.4.3

Internal circuits

Fig. 3.4:
Inputs and test pulses at an MSI 410 module
Fig. 3.5:
Outputs at an MSI 410 module
3.4.4

Limited short-circuit detection in the input circuits

Ä One MSI 4xx module has four test signal generators T1 – T4.
Ä Short-circuits between test signal generators of a MSI 4xx module are detected. Short circuit
detection is only ensured between different modules if the test gaps of the test signal gener-
ators are < 4 ms, the test periods ≥ 200 ms. Short-circuits past 24 V DC (after High) at in-
puts that are connected to test outputs are detected independently of the length of the test
gaps.
Make note of this during wiring (e.g. through separate routing or protected lines)!