4.2.2

Inductive safety switches

Tab. 4.17:
Inductive safety switch connection
Electrical connection: Example from MSI.designer
Inductive switch
(serial)
Inductive switch
Tab. 4.18:
Functions with inductive safety switches
Function
Testing
Series connection/
cascading
NOTICE
You can find additional information in the operating instructions for the inductive safety switches.
i
4.2.3

Transponder switches

Tab. 4.19:
Transponder connection
Electrical connection: Example from MSI.designer
With OSSD
Tab. 4.20:
Functions with transponders
Function
Series connection/
cascading
NOTICE
You can find additional information in the operating instructions for the respective transponder
i
switch.
Leuze electronic
Info
Necessary with serial inductive switches
Inductive switches (serial):
Up to six sensors per input. Maximum OFF-ON delay of the
cascade is 10 ms (otherwise, the test gap will lead to switch-
off). Note the maximum line resistance of 100 Ω and the correct
setting of the test pulse time.
Inductive switch: No cascading possible
Info
Possible, depending on type used
Test input TE at T1
Output A at I5
OSSD1 on I7
OSSD2 on I8
OSSD1 at I1
OSSD2 at I2
MSI 400
Connecting devices
47