Configure Volume Flow Type For Gas Applications; Configure Standard Gas Density - Emerson Micro Motion 2700 Configuration And Use Manual

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

4.3.1

Configure Volume Flow Type for gas applications

Display
ProLink II
ProLink III
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Standard Gas Volume
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement is
used.
Restriction
If you are using the petroleum measurement application, you must set Volume Flow Type to Liquid. Gas
standard volume measurement is incompatible with the petroleum measurement application.
Restriction
If you are using the concentration measurement application, you must set Volume Flow Type to Liquid.
Gas standard volume measurement is incompatible with the concentration measurement
application.
Procedure
Set Volume Flow Type to Gas Standard Volume.
4.3.2

Configure Standard Gas Density

Display
ProLink II
ProLink III
Field Communicator Configure > Manual Setup > Measurements > GSV > Gas Ref Density
Overview
The Standard Gas Density value is used to convert the measured flow data to the standard
reference values.
Prerequisites
Ensure that Density Measurement Unit is set to the measurement unit you want to use for
Standard Gas Density.
Configuration and Use Manual
Not available
ProLink > Configuration > Flow > Vol Flow Type
Device Tools > Configuration > Process Measurement > Flow
Not available
ProLink > Configuration > Flow > Std Gas Density
Device Tools > Configuration > Process Measurement > Flow
Configure process measurement
35