Emerson Micro Motion 2700 Configuration And Use Manual page 16

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Quick start
1.
2.
Table 2-1:
Transmitter status reported by status LED
LED state
Description
Green
No alarms are active.
(1)
Flashing green
No alarms are active. One or more previously
active alarms have not been acknowledged.
Yellow
One or more low-severity alarms are active,
and have been acknowledged.
(2)
Flashing yellow
One or more low-severity alarms are active
and have not been acknowledged.
Red
One or more high-severity alarms are active,
and have been acknowledged.
(3)
Flashing red
One or more high-severity alarms are active
and have not been acknowledged.
Postrequisites
For information on viewing the list of active alarms, see
For information on individual alarms and suggested resolutions, see
(1) If Status LED Blinking is disabled, the LED will show solid green rather than flashing.
(2) If Status LED Blinking is disabled, the LED will show solid yellow rather than flashing.
(3) If Status LED Blinking is disabled, the LED will show solid red rather than flashing.
8
Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and
checks for error conditions. During the power-up sequence, Alarm A009 is active.
This alarm should clear automatically when the power-up sequence is complete.
Check the status LED on the transmitter.
Recommendation
Continue with configuration or process meas-
urement.
Continue with configuration or process meas-
urement. If you choose, you can acknowledge
the alarms.
A low-severity alarm condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or proc-
ess measurement. If you choose, you can iden-
tify and resolve the alarm condition.
A low-severity alarm condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or proc-
ess measurement. If you choose, you can iden-
tify and resolve the alarm condition. You may
also acknowledge the alarm.
A high-severity alarm condition affects meas-
urement accuracy and output behavior. Re-
solve the alarm condition before continuing.
A high-severity alarm condition affects meas-
urement accuracy and output behavior. Re-
solve the alarm condition before continuing.
You may also acknowledge the alarm.
Section
®
Micro Motion
Model 2700 Transmitters with Analog Outputs
9.4.
Section
12.2.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents