Integrate the meter with the control system
6.4.2

Configure Discrete Output Polarity

Display
ProLink II
ProLink III
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Polarity
Overview
Discrete outputs have two states: ON (active) and OFF (inactive). Two different voltage
levels are used to represent these states. Discrete Output Polarity controls which voltage level
represents which state.
Procedure
Set Discrete Output Polarity as desired.
The default setting is Active High.
Options for Discrete Output Polarity
Table 6-10:
Polarity
Active High
Active Low
118
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > DO POLAR
ProLink > Configuration > Frequency/Discrete Output > Discrete Output > DO Polarity
Device Tools > Configuration > I/O > Outputs > Discrete Output
Options for Discrete Output Polarity
Micro Motion
Description
When asserted (condition tied to DO is
true), the circuit provides a pull-up to 24 V.
When not asserted (condition tied to DO is
false), the circuit provides 0 V.
When asserted (condition tied to DO is
true), the circuit provides 0 V.
When not asserted (condition tied to DO is
false), the circuit provides a pull-up to 24 V.
®