Electrical Installation
5 Electrical Installation
5.1 How to Connect
5.1.1 Cables General
NOTE
For the AKDHigh Power series mains and motor connections, please see the ADAP-KOOL
Operating Instructions, MG.11.Ox.yy.
NOTE
Cables General
Always comply with national and local regulations on cable cross-sections.
Details of terminal tightening torques.
Power (kW)
Enclo-
200-240
sure
V
A2
1.1 - 3.0
A3
3.7
A4
1.1 - 2.2
A5
1.1 - 3.7
B1
5.5 - 11
-
B2
15
C1
18.5 - 30
37
C2
45
Table 5.1 Tightening of terminals
®
ADAP-KOOL
Drive Operating Instructions
380-480
Line
V
1.1 - 4.0
1.8
5.5 - 7.5
1.8
1.4 - 4
1.8
1.1 - 7.5
1.8
11 - 18.5
1.8
22
2.5
30
4.5
37 - 55
10
75
14
90
24
MG.11.L4.02 - ADAP-KOOL
Torque (Nm)
DC
Motor
Brake
connection
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.5
2.5
3.7
4.5
3.7
10
10
14
14
24
14
®
Drive
®
Drive AKD102High Power
Earth
Relay
1.8
3
0.6
1.8
3
0.6
1.8
3
0.6
1.8
3
0.6
1.5
3
0.6
3.7
3
0.6
3.7
3
0.6
10
3
0.6
14
3
0.6
14
3
0.6
5
5
25