Danfoss ADAP-KOOL AKD 102 Operating Instructions Manual page 64

Hide thumbs Also See for ADAP-KOOL AKD 102:
Table of Contents

Advertisement

How to Programme the Frequ...
7.1.3 Function Setups
The Function set-up provides quick and easy access to all parameters required for the majority of ADAP-KOOL applications
including most VAV and CAV supply and return fans, cooling tower fans, Primary, Secondary and Condenser Water Pumps
and other pump, fan and compressor applications.
How to access Function Set-up - example
How to change the output on "Analog output 42"
Illustration 7.2 Step 1: Turn on the frequency converter (yellow
LED lights)
7
7
Illustration 7.3 Step 2: Press the [Quick Menus] button (Quick
Menus choices appear).
Illustration 7.4 Step 3: Use the up/down navigation keys to scroll
down to Function Setups. Press [OK].
Illustration 7.5 Step 4: Function Setups choices appear. Choose
03-1 General Settings. Press [OK].
Illustration 7.6 Step 5: Use the up/down navigation keys to scroll
down to i.e. par. 03-11 Analog Outputs. Press [OK].
64
®
ADAP-KOOL
Drive Operating Instructions
Illustration 7.7 Step 6: Choose par. 6-50 Terminal 42 Output. Press
[OK].
Illustration 7.8 Step 7: Use the up/down navigation keys to
select between the different choices. Press [OK].
®
MG.11.L4.02 - ADAP-KOOL
Drive

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADAP-KOOL AKD 102 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents