Conversion Instructions
Example
0000
07
D00030
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1
D00031
0 1 0 0 0 0 0 0 1 0 0 1 0 1 0 1
D00040
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
5-17-13

COLUMN TO LINE: LINE(115)

Ladder Symbol
(115)
LINE
S
Variations
j LINE(115)
Description
Bit
15
S
0 0 0 0 1 1 1 0 0 0 1 0 0 0 0 1
S+1
1 1 0 1 0 0 1 0 0 1 1 1 0 0 0 1
S+2
0 0 0 1 1 0 1 1 0 0 1 0 0 1 1 1
S+3
1 0 0 0 0 0 1 1 0 0 0 0 0 1 1 1
.
.
.
S+15
0 1 1 1 0 0 0 1 1 0 0 0 1 0 1 0
Precautions
When CIO 000007 is ON in the following example, all ON bits in D00030 and
D00031 are counted and the results is placed in D00040.
(114)
BCNT
#0002
D00030
Before
execution
0
0
0
F
4
0
9
5
0
0
0
0
Bi
D
When the execution condition is OFF, LINE(115) is not executed. When the
execution condition is ON, LINE(115) copies bit column Bi from the 16-word set
S through S+15 to the 16 bits of word D (00 to 15), i.e., bit Bi of S+n is copied to bit
n of D, for n=00 to 15. In the following example, Bi would be 5.
Bi
.
.
.
.
.
.
S cannot be one of the last 15 words in a data area because it designates the first
of 16 words.
Bi must be BCD between 0000 and 0015.
Note Refer to page 115 for general precautions on operand data areas.
D00040
After
execution
0
D00030
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1
4
D00031
0 1 0 0 0 0 0 0 1 0 0 1 0 1 0 1
0
D00040
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
Operand Data Areas
st
S: 1
source word
CIO, G, A, T, C, DM
Bi: Bit designator
CIO, G, A, T, C, #, DM, DR, IR
D: Destination word
CIO, G, A, DM, DR, IR
Bit
00
.
.
.
Bit
15
D
0
Section 5-17
Address Instruction
00000
LD
00001
BCNT(114)
0
0
F
0
9
5
0
0
9
Bit
00
. . .
0 1
1
1
Operands
000007
#0002
D00030
D00040