1 Introduction
1-2-2
Branch Line and Multidrop Support for Cable Types and Baud
Rates
Support for Branch Lines
Support for branch lines from the trunk line or sub-trunk lines and support for sub-branch lines from
branch lines is listed in the following tables.
• Baud Rate of 4 Mbps (No Branch Lines)
Round Cable I
Round Cable II, Flat Cable I, or Flat
Cable II
Note Branch lines are not supported for a baud rate of 4 Mbps and therefore Slave Units with Prewired Cables
cannot be used. The network must consist of Slave Units without Cables, and multidrop connections must be
used. (DCN4-MD4 Multidrop Connectors must be used for Flat Cable I.)
• Baud Rate of 3 Mbps
Round Cable I
Round Cable II, Flat Cable I, or Flat
Cable II
• Baud Rate of 1.5 Mbps
Round Cable I
Round Cable II, Flat Cable I, or Flat
Cable II
• Baud Rate of 93.75 kbps
Round Cable I
Round Cable II, Flat Cable I, or Flat
Cable II
Support for Multidrop Connections
• All Baud Rates
You cannot use multidrop connections if you use Flat Cable II because there are no Multidrop Con-
nectors for Flat Cable II.
1-14
Cable
Not supported
Not supported
Cable
Supported
Supported
Cable
100 m max.
Not supported
30 m max.
Supported
Supported
Cable
Supported
Supported (no restrictions)
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
Branch lines
Not supported
Not supported
Branch lines
Not supported
Not supported
Branch lines
Not supported
Supported
Branch lines
Not supported
Sub-branch lines
Sub-branch lines
Sub-branch lines
Sub-branch lines