Error Messages - Omron SYSMAC CV Series Operation Manual

Ladder diagrams
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

Error Messages

Error
I/O table error
CPU Bus Unit error
SYSMAC BUS/2 error
SYSMAC BUS error
Battery error
CPU Bus Unit setting error The registered CPU Bus Unit
Momentary power
interruption
SFC Non-fatal Errors
Error
Overlapping action
0001
execution
S-group AQ overuse
0002
(Note)
Overlapping S-group
0003
AQ execution (Note)
506
Probable cause
Unit has been removed making
I/O table incorrect.
A parity error has occurred in the
transfer of data between the
CPU and a CPU Bus Unit or in
the CPU Bus Link.
An error has occurred between a
Master and Slave Rack.
An error has occurred between a
Master and Slave Rack.
CPU or Memory Card backup
battery is missing or its voltage
has dropped.
number doesn't agree with the
registered unit number.
A momentary power interruption
can be set as an non-fatal error
in the PC Setup.
Note
1. Error codes 0200 to 0215 indicate CPU Bus Units #00 to #15, respectively,
while 0231 indicates a CPU bus link error. Also, A422 contains the errant
Unit's number, and A42315 is turned ON to indicate a CPU bus link error.
2. A424 contains the unit number of the Master involved, and A480 to A499
contain the unit number of the Slave involved.
3. A425 contains the unit number of the Master involved, and A470 to A477
contain the unit number of the Slave involved.
4. A42615 is turned ON to indicate a battery error, and A42614 is turned ON to
indicate a Memory Card battery error.
5. Error codes 0400 to 0415 indicate CPU Bus Units #00 to #15, respectively,
while 0431 indicates a CPU Bus Link error. Also, A427 contains the errant
Unit's number.
The following table describes SFC non-fatal errors. When an SFC non-fatal er-
ror occurs, the SFC Non-fatal Error Flag (A40211) is turned ON, and the error
code is output to A418.
Error code
(A418)
The program attempted to execute the same
action from more than one step at the same
time.
The program attempted to simultaneously
execute 128 or more actions with S-group AQs.
Any actions that exceed the maximum
allowable 127 will not be executed.
The program attempted multiple execution of
the same action having an S-group AQ.
Flag(s)
Error code
(A400)
A40209 00E7
A40207 0200 to 0215
1
or 0231
A40206 00B0 to 00B3
(Masters
#0 to #3.)
A40205 00A0 to 00A7
(Masters
#0 to #7.)
A40204 00F7
A40203 0400 to 0415
5
or 0431
A40202 0002
Probable cause
Section 8-4
Possible remedy
Check the I/O table from the
CVSS/SSS and either
connect Dummy I/O Units or
correct the I/O table.
Check the errant Unit.
Verify that the Slave Rack is
operating properly, and
2
check the transmission line.
Verify that the Slave Rack is
operating properly, and
3
check the transmission line.
Check battery and replace if
4
necessary.
Check the errant Unit.
Check the power supply
voltage and lines.
Possible remedy
Check the program. If you
wish, you can make a PC
system setting so that
overlapping action execution
will not generate an error.
With the default setting, this
non-fatal SFC error is
generated.
Check the program. S-group
AQs include S, SL, SD, and
DS.
Check the program.